SlopeShield Testing

 Printer Friendly (PDF)
ICC-ES AC48 and AC207 Approval English (PDF, 351kb)

Approvals and Testing

Acceptance Criteria for Polypropylene Roof Underlayments AC 207 & Acceptance Criteria for Roof Underlayments for use in severe climate areas AC48. Tested in accordance with ICC-ES AC 48 and AC 207 criteria to meet UBC, IBC and IRC requirements for Roofing Underlayments.

PROPERTYSTANDARD/TESTRESULT RESULT RESULT
Tensile Strength

ASTM D1682
AC 48, Section 4.1

Control
MD – 106.7 lbf/inch
(18.7 N/mm)
XMD – 83.8 lbf/inch
PASS
Accelerated Aged
MD – 107.0 lbf/inch
(18.7 N/mm)
XMD – 81.4 lbf/inch
PASS
 UV Exposed
MD – 97.3 lbf/inch
(17.0 N/mm)
XMD - 76.7 lbf/inch
PASS

Water Vapor Transmission and Permeance

ASTM E96*
(Water Method)
AC 207, Section 4.1

406.3 g/m² 24hrs
3374.8 ng/Pa/s/m²
59 Perms
PASS
   
Air Permeance

ASTM E2178

0.009 L/s/m2
0.0019 cfm/ft2
PASS
   

Water Ponding

AC 48, Section 4.4
24" head of water for 48 hrs.

PASS    
Accelarated Aging

AC48, Section 4.7
AC207, Section 4.6

PASS    

UV Exposure

AC48, Section 4.8
AC207, Section 4.7

PASS    

Liquid Water Transmission

ASTM D4869
AC207, Section 4.3
Showerhead impinges 40 to 42 gallons of water per hour for 4 hrs on sample.

PASS    

Rupture Resistance

ASTM D3462
AC207, Section 4.4

PASS    

Pliability

ASTM E48
AC 207, Section 4.2

PASS    


*ASTM E 96 - Method B (wet cup method) typically gives a more realistic result for permeance than does the Method A (dry cut/desiccant) method.


Application

ROOF SLOPESLOPESHIELD WITH INTEGRATED TAPESLOPESHIELD SA SELF-ADHERED
1:12 to 2:12 For slip sheet applications only (No water hold out) For slip sheet applications only (No water hold out)
2:12 to 3:12 For slip sheet applications only (No water hold out) • Apply as Underlayment
• 12" Horizontal/Vertical Lap Seams
• VaproTape required under metal clips and similiar penetrations 
3:12 to 4:12 • Apply as Underlayment
• Vertical Installation Only (Metal Roofing)
• VaproTape required under metal clips and similiar penetrations 
• Apply as Underlayment
• 12" Horizontal/Vertical Lap Seams
• VaproTape required under metal clips and similiar penetrations 
4:12 and greater • Apply as Underlayment
• 6" Vertical Lap as per the Integrated Tape
• VaproTape required under metal clips and similiar penetrations 
• Apply as Underlayment
• 6" Horizontal/Vertical Lap Seams
• VaproTape NOT required for clips 


For slate tile or other roofing applications Contact VaproShield for review and approval. 

SlopeShield is not to be used as a temporary roof covering during the construction period. SlopeShield can sustain up to 4 months of UV exposure but is not intended to be the primary liquid water hold out barrier. Temporary protection measures such as tarps must be used when rain, snow/ice or storm events exist or are anticipated.

 